    1.变频器上电瞬间即跳闸

      变频器上电时,因变压器的激磁涌流和单元电容充电,瞬时电流有效值最高可达到变频器额定电流的6-7倍,持续时间几十毫秒;若变频器上级电流保护整定值过小,会造成上级开关速断保护跳闸。
      调整上级开关柜速断保护整定值。
      本地或远程的急停按钮,是否处于正常分断状态。
      查看人机界面是否存在故障显示内容,否则请检查高开柜内部跳闸回路。

     

    2.启动过程中输出频率在低速震荡,无法加频

      有些电机在低速时,因为齿槽效应等影响,电流波动非常大,此时变频器可能出现限流,使得变频器出现加速、限流减速等反复,而无法正常加速。